IMPORTANT – PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING.
Products Covered: RC7STC, RC7ATC, RC7ATJTC, RC7CTC, RC7CTJTC, and RC7SHTC
RC7ATC-LJB, RC7ATJTC-LJB, RC7ATCLJB25 and RC7ATJTCLJB25
CAUTION: Do Not operate tile stripper or resurfacing equipment over top of covers. This may result in damage to the surface finish of the product.
Suitable for use in air handling spaces in accordance with Sec. 300-22 (C) of the National Electrical Code.
Step 1. Layout and locate position of hole(s). Step 2. Remove 6 1/2" [165mm] section from carpet
or tile. Use template provided.
CAUTION: Holes shall be spaced a minimum of 2' [610mm]
on center and not more than one hole per each
65 sq. ft. [6 sq. m] of floor area in each span.
For Tile Applications up to a Maximum of 3/4" [19.1mm] Thick.
NOTE: Be certain to drill hole at least 4" [102mm] from any wall NOTE: For tile thickness greater than 3/4" [19.1mm] consult factory.
or pillar to leave enough room for Poke-Thru cover assembly.
Step 3. Core drill hole. Step 4. Stem Assembly: Step 5. Cover Assembly:
Catalog No. RC7STC. Catalog No. RC7CTC
Insert stem into hole. or RC7CTJTC. Remove
disposable plate and replace
with carpet/tile flange. Install
with four #6-32 x 1/4"
[6.4mm] FHMS.
24" [610mm] Min
Center – Center
6 1/2"
[165mm] Diameter
CAUTION: Poke-Thru cannot be rotated
in hole after insertion into floor.
3" Diameter Core Drill
3 1/16" [78mm] Actual Diameter
Push Down
Four #6-32
x 1/4" FHMS
RC
7
Poke-Thru Series
INSTALLATION INSTRUCTIONS
Installation Instruction No.: 1 001 628 R2 – Updated April 2005
Wiremold Electrical Systems conform to and should be installed
and properly grounded in compliance with requirements of the
current National Electrical Code, Canadian Electrical Code or
codes administered by local authorities.
All electrical products may represent possible shock or fire hazard
if improperly installed or used. Wiremold electrical products are
UL Listed to U.S. and Canadian safety standards, made for
interior use only, and should be installed in conformance with
current local and/or the National Electrical Code.
Page view 0
1 2 3 4 5 6

Summary of Contents

Page 1 - Poke-Thru Series

IMPORTANT – PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING.Products Covered: RC7STC, RC7ATC, RC7ATJTC, RC7CTC, RC7CTJTC, and RC7SHTC RC7ATC-LJB, RC7ATJ

Page 2

Complete Assembly:Step 6. Cat. Nos. RC7ATC or RC7ATJTC Step 7. Wire the power circuit. Wire the Poke-Thru device. (Can be completed above floor.)Refe

Page 3

3Step 10. Wire and snap communication Step 11. For cable pass-through or empty jacks in adapters as shown. communication port, install foam block in

Page 4

4Step 14. Attach slide cover with two #6-32 screws. Step 15. Push Poke-Thru unit into concrete Pass-through cabling must pass through to complete in

Page 5

The RC7TC Series Poke-Thru Device is UL Listed and Classified to U.S. and Canadian safety standards to the following conditions: The RC7STC Poke-Thru

Page 6 - Carpet Cutout Template

Wiremold / LegrandU.S. and International: 60 Woodlawn Street • West Hartford, CT 061101-800-621-0049 • FAX 860-232-2062 • Outside U.S. 860-233-6