Suitable for use in air handling spaces in accordance with Sec. 300-22 (C) of the National Electrical Code.
Step 1. Layout and locate position of hole(s). Step 2. Core drill hole.
CAUTION: Holes shall be spaced a minimum of 2' [610mm]
on center and not more than one hole per each
65 sq. ft. [6 sq. m] of floor area in each span.
NOTE: Be certain to drill hole at least 4" [102mm] from any wall
or pillar to leave enough room for poke-thru cover assembly.
Step 3. Carpet Option.
Remove section from carpet using disposable plate or template.
RC9FFS, RC9AFFTC, 291-H/BTC,
292-H/BTC, RC91GHBTC, RC92GHBTC,
and RC9CFFTC
INSTALLATION INSTRUCTIONS
Installation Instruction No.: 1 001 997 R2 – Updated July 2005
Wiremold Electrical Systems conform to and should be installed
and properly grounded in compliance with requirements of the
current National Electrical Code, Canadian Electrical Code or
codes administered by local authorities.
All electrical products may represent possible shock or fire
hazard if improperly installed or used. Wiremold electrical
products are UL listed. Made for interior use only and should be
installed in conformance with current local and/or the National
Electrical Code.
24" [610mm] Min
Center – Center
3" Diameter Core Drill
3 1/16" [78mm] Actual Diameter
RC91GHBTC, RC92GHBTC,
291-H/BTC, 292-H/BTC
Style Service Heads
(Carpet Only)
RC9AFFTC, RC9CFFTC
6 1/2" [165mm] Diameter
Cutout (Carpet Only)
Make Concentric with Intended Core Hole
IMPORTANT: Please read all instructions
before beginning.
Page view 0
1 2 3 4 5 6

Summary of Contents

Page 1 - RC9FFS, RC9AFFTC, 291-H/BTC

Suitable for use in air handling spaces in accordance with Sec. 300-22 (C) of the National Electrical Code. Step 1. Layout and locate position of hole

Page 2 - Push Down

Step 4. Tile Option.For RC9CFFTC and RC9AFFTC, cut a clearance hole in tile floor covering between 3 1/16" [78mm] and 4" [102mm] diameter.NO

Page 3 - Separately, Install Stem

Step 3. Install outlets, communication devices Step 4. Attach cover plate using and corresponding faceplates. the #8-32 screws provided. NOTE: If

Page 4

4Step 2: Remove disposable plate from poke-thru Step 3: Attach 1/2" trade size conduit fitting stem. Place trim flange and hex housing (not p

Page 5

The RC9 Pedestal/Furniture Feed Series Poke-Thru Devices are UL Listed and Classified to U.S. and Canadian safety standards to the following condition

Page 6 - Carpet Cutout Template

Wiremold / LegrandU.S. and International: 60 Woodlawn Street • West Hartford, CT 061101-800-621-0049 • FAX 860-232-2062 • Outside U.S. 860-233-6