Legrand AL2040A Aluminum Surface Raceway User Manual

Browse online or download User Manual for Hardware Legrand AL2040A Aluminum Surface Raceway. Legrand AL2040A Aluminum Surface Raceway User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 4
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
AL2400 RACEWAY WIRE FILL CAPACITIES FOR DATA/COMMUNICATION
OD
CABLE/WIRE SIZE [In.] [mm] 20% FILL* 40% FILL**
UNSHELDED 4-pair, 24 AWG, Cat. 5 0.220 [5.6] 8 17
TWISTED PAIR 4-pair, 24 AWG, Cat. 3 0.190 [4.8] 11 23
4-pair, 24 AWG, Cat. 6 0.250 [6.3] 6 13
TELEPHONE 2-pair, 24 AWG 0.140 [3.6] 22 44
3-pair, 24 AWG 0.150 [3.8] 19 38
4-pair, 24 AWG 0.190 [4.8] 11 24
25-pair, 24 AWG 0.410 [10.4] 2 5
COAXIAL RG58/U 0.195 [5.0] 11 22
RG59/U 0.242 [6.1] 7 14
RG62/U 0.242 [6.1] 7 14
RG6/U 0.270 [6.9] 5 11
TWINAXIAL 100 Ohm 0.330 [8.4] 3 7
SHELDED Type 1 0.390 [9.9] 2 5
TWISTED PAIR Type 2 0.465 [11.8] 2 4
Type 3 0.245 [6.2] 7 14
AL2400 Aluminum
Surface Raceway
INSTALLATION INSTRUCTIONS
Installation Instruction No.: INST007 R1 – Updated October 2003
AL2400 RACEWAY WIRE FILL CAPACITIES FOR POWER
WIRE TYPE TW THW RHH/RHW THHN/THWN
POWER WIRING 6 AWG 8 8 5 13
WITHOUT DEVICE 8 AWG 14 11 8 18
1.7 sq. in. cross section 10 AWG 31 22 15 37
12 AWG 40 27 24 58
14 AWG 50 33 30 78
POWER WIRING AWG 6 AWG 3
WITH DEVICE 8AWG 3 4
5-20R duplex devices 10 AWG 6 5 3 8
1.35 sq. in. cross section 12 AWG 8 6 5 12
14 AWG 10 7 6 16
NOTE:* 20% cable fill is calculated to approximate reduction in cable capacity due to connectors mounted within raceway and fittings that may restrict
cross sectional area.
** 40% cable fill is the maximum designed cable fill base on a proposed revision to TIA/EIA 569-A.
Wiremold Electrical Systems conform with, and should be installed and
properly grounded in compliance with requirement of the current
National Electrical Code or codes administered by local authorities.
All electrical products may represent a possible shock or fire hazard
if improperly installed or used. Wiremold electrical products are UL list-
ed, made for interior use and should be installed by qualified
electrical people in conformance with current local and/or the
National Electrical Code.
Note: Raceway may be configured in single or multiple channels
to accommodate power or communications wiring.
MAXIMUM CROSS SECTION
Without Device
1.5 sq. in.
[38mm]
2"
[51mm]
1 9/32"
[33mm]
With 5-20R
1.35 sq. in.
[34mm]
Page view 0
1 2 3 4

Summary of Contents

Page 1 - Surface Raceway

AL2400 RACEWAY WIRE FILL CAPACITIES FOR DATA/COMMUNICATIONODCABLE/WIRE SIZE [In.] [mm] 20% FILL* 40% FILL**UNSHELDED 4-pair, 24 AWG, Cat. 5 0.220 [5.6

Page 2 - AL2451H BOX ADAPTER

AL2400B BASE and AL2400C COVERAL2401 COUPLINGAL2409 GROUND ADAPTERAL2451H BOX ADAPTERAt AL2400B base section butt joints, slide AL2401 Couplinginto fl

Page 3 - AL2410B2 FEED END FITTING

AL2410B BLANK END FITTINGAL2410B2 FEED END FITTINGAL2440A IN-LINE SINGLE POLE SWITCHAt end of AL2400B Raceway run, slide AL2410B2 Feed Endin last base

Page 4 - AL2418 EXTERNAL ELBOW

AL2411 90° FLAT ELBOW AL2417 INTERNAL ELBOWAL2415 TEE ELBOWAL2418 EXTERNAL ELBOWAL2400WC WIRE CLIPAt 90° turn on same surface, position AL2411 Flat El

Comments to this Manuals