Legrand SPMJ SpecMate Wireway Systems User Manual

Browse online or download User Manual for Hardware Legrand SPMJ SpecMate Wireway Systems. Legrand SPMJ SpecMate Wireway Systems User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 2
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
SpecMate
Wireway Systems
INSTALLATION INSTRUCTIONS
SpecMate Type 1 Wireway is provided in sizes ranging
from 2" to 24" [51mm to 610mm] wide and from 2" to
12" [51mm to 305mm] deep, with a hinged cover. The
Wireway may be provided with barriers. All SpecMate
Wireway is listed by Underwriters Laboratories under
File No. E137690 and CSA Certified under File No.
LL59760 in compliance with the National and Canadian
Electrical Code.
Typical Installation: The Wireway shall be installed as a complete system incorporating all fittings necessary to provide for directional
changes. All connections shall be fastened securely with the fasteners provided by the manufacturer in order to ensure compliance with
UL and CSA bonding requirements. Conductors of appropriate types as outlined by the applicable Electrical Code may be used in the
Wireway following installation. Specific installation instructions are given below.
Hanging Method: Three styles of hangers may be purchased with SpecMate Wireway Systems.
“C” Hanger: For widths up to 12" [305mm]. Trapeze Hanger: For any size of Wireway.
Wall Bracket: For installations along walls.
For any size of Wireway.
Installation of couplings:
Installation of end blanks:
Coupling: Couplings are provided with necessary hardware. Slide
the coupling into the end of the wireway and tighten the fasteners with
a wrench, ensuring they are secure. Slide the end of the next length of
wireway over the other half of the coupling and attach the fasteners.
Repeat until complete. Couplings are best located at 1/4 of the dis-
tance between supports (hangers).
End Blank: End blanks provided with necessary hardware. Slide the
end blank into the end of the wireway and tighten the fasteners with a
wrench, ensuring they are secure.
Installation: For “C” Hangers, Trapeze Hangers, threaded rod should be cut to the appropriate length and fastened to a structural
member. The hanger should then be bolted to the threaded rod through the holes provided, ensuring that it is level and in line with the
other hangers. Wall-mounted hangers should be fastened to structural members in the wall in a manner ensuring sufficient support
strength. Once the Wireway is in place, it must be fastened to the hanger by any structurally sound method. Most installations use
1/4" [6.4mm] nuts and bolts, fastened through holes drilled in the Wireway Base. No sharp edges shall be allowed in the Wireway as
a result of fastening. Fastening hardware for hangers is not provided. UL listed Wireway with square cross sections of 2.5, 4, and 6
inches [64, 102 and 152mm] may be supported on maximum spans of 10 feet [3 meters]. All other Wireway shall be supported on
spans of 5 feet [1.5 meters] or less.
u c
Page view 0
1 2

Summary of Contents

Page 1 - Wireway Systems

SpecMate™Wireway SystemsINSTALLATION INSTRUCTIONSSpecMate Type 1 Wireway is provided in sizes rangingfrom 2" to 24" [51mm to 610mm] wide and

Page 2

Smaller Inside Dimensions of Wireway Maximum Conductor Size AWG or MCMInches [mm] Conductor [mm2]1 1/4 31.8 6 13.32 50.8 3 26.72 1/2 63.5 2 33.63 76.2

Comments to this Manuals

No comments