To Install on PK Presets:
1. Cut a 5 5/8" [143mm] x 6 3/4" [171mm] long
(along length of cell run) opening in carpet exactly
centered over preset. (Save for later abandoning).
Remove concrete and mudcap from preset and
grout as required.
2. Use a screwdriver to remove only one power
knockout from cell, then install power grommet.
3. Snap communications cell grommets in place
(refer to instruction sheet 1 000 684).
4. Route electrical conductors and/or communication cables.
5. Attach enclosure to preset and partition to leveling ring.
6. Install leveling ring so top surface will be approximately
1/16" [1.6mm] below top of carpet. Install access covers
(M4 only). Attach base of fitting to leveling ring so that base
is tight against both carpet and ring.
7. Install round grommet and mounting frame into base. Install
partition to separate services if needed. (MP8
size only). Install ground wire between base
and enclosure.
8. Install UL Listed wiring devices and/or communication
services. Cut off excess length on electrical device mount-
ing screw (top screws only). Attach faceplates over each
opening and screw on cover.
Multiplex
Service Fitting
INSTALLATION INSTRUCTIONS
Installation Instruction No.: IB0123 R1 – Updated September 2006
PK Series
Cover
Base
Leveling Ring
Partition
Enclosure
Communications Grommet
Power Grommet
Access Cover
Mounting Frame
Faceplate
PK Preset
Wiremold / Legrand electrical systems conform to and should be
properly grounded in compliance with requirements of the current
National Electrical Code or codes administered by local authorities.
All electrical products may present a possible shock or fire
hazard if improperly installed or used. Wiremold / Legrand electrical
products may bear the mark as UL Listed and/or Classified and should
be installed in conformance with current local and/or the National
Electrical Code.
IMPORTANT: Please read all instructions
before beginning.
Page view 0
1 2 3 4

Summary of Contents

Page 1 - Service Fitting

To Install on PK Presets:1. Cut a 5 5/8" [143mm] x 6 3/4" [171mm] long (along length of cell run) opening in carpet exactly centered over p

Page 2 - N-R-G Series

Instructions to Install on N-R-G Presets:1. Install closure plate over unused opening, if needed.2. Snap communication cell grommets in place (refer t

Page 3 - Walkerduct Pro Series Preset:

Install on 2" [51mm] IPS Presets or Aftersets:1. Determine location of insert using any of the following methods:a. Using an electronic insert f

Page 4 - Figure 2

Walkerduct Pro Series™Mudcap and Knockout Removal:1. Use a Walker insert finder (Cat. No. 480) or other electronic locator to find center of preset.